2624 Richmond Rd - DEMO REPORT
Victoria, BC, V8R T28
Home Inspection Report
Inspection
Property
Address
Occupancy
Home Details
Inspection
Inspector
Identity
Contact
Credentials
Inspection
Client
Identity
Contact
Inspection
Realtor
Identity
Contact
Company
Inspection Summary
This summary highlights findings that may be significant, including potential safety concerns, items that may require major expense to correct, and other conditions the inspector wants to bring to the client's attention.
The summary is not a complete list of every finding in the report and reflects the inspector's professional opinion at the time of inspection. Clients should review the full report, as the summary alone does not explain all inspected areas or all reported conditions.
Repairs or further evaluation should be completed by qualified and, where required, licensed professionals. Clients should retain receipts, warranties, permits, and related documentation for any completed work.
Critical Findings
-
Granular Degradation Shingles
Roof shingles show wear and granular degradation. The roof is nearing the end of its 20‑year lifespan. Have a qualified roofer evaluate the roof and plan needed repairs.
-
Incomplete Roof Flashing
Roof flashing is incomplete. Incomplete flashing can allow water intrusion. Repair the flashing promptly.
-
Disconnected Upper Gutter Downspout
Upper gutter downspout is not connected to lower gutters and spills onto lower roof shingles. Improper drainage can wet the shingles. Connect the downspout to the gutters to restore proper drainage.
-
Missing Kitchen Smoke Detector
A smoke detector is missing in the kitchen. The kitchen lacks fire detection coverage. Install a smoke detector to restore required safety.
-
Improper Duct Connection
Ducting is not connected properly and attic ventilation is insufficient. This can cause poor airflow and potential moisture buildup. Repair the duct connections and improve attic ventilation promptly.
-
2013 Electrical Hot Water Tank
Electrical hot water tank installed in 2013 is past its 10‑year recommended life span. Operating beyond recommended life may affect reliability. Have a qualified professional evaluate the tank.
Medium Findings
-
Large Driveway Crack
A large crack is present in the driveway. The crack may allow water infiltration and further deterioration. Repair the crack to restore the driveway surface.
-
Roof Corner Rot
Roof corner shows rot. Rot can compromise structural integrity. Repair the affected area to restore roof condition.
-
Roof Fascia Rot
Roof fascia is rotten. Rot can permit water intrusion and degrade the roof edge. Replace the fascia to restore proper protection.
-
Rusty Roof Nails
Rusty nails are on the roof and caulking is missing. This can allow corrosion and water intrusion. Have a technician service the roof to replace nails and apply caulking.
-
Clogged Gutters
Gutters are clogged. This can prevent proper drainage and cause water overflow. Clean the gutters to restore drainage.
-
Rufet Height Below Standard
Rufet height is under 18 inches. This fails the standard height requirement. Have a qualified contractor evaluate and adjust the height to meet the standard.
-
Improperly Installed Downspout
Downspout is not installed correctly on the roof. Improper installation can prevent proper drainage of roof runoff. Have a qualified contractor repair the downspout to ensure correct drainage.
-
Improperly Installed Downspout
Downspout is not properly installed. This may affect drainage of roof runoff. Repair the installation to restore proper drainage.
-
Aluminum Siding Soil Contact
Aluminum siding contacts soil with no clearance. This can permit moisture intrusion. Have a contractor evaluate and repair to create a proper gap.
-
Stucco Crack Below Window
Crack observed in stucco below exterior window corner. The crack may allow water intrusion. Repair the crack to prevent moisture entry.
-
Exterior Window Seal Defect
Caulking and sealing on the exterior window needs service, creating potential for water ingress. Water ingress could enter the building through the compromised seal. Repair the caulking and sealing to prevent water entry.
-
Kitchen Window Seals
Window seals in the main kitchen area are past the end of their lifespan. The seals no longer effectively prevent air or water infiltration. Replace the window seals.
-
Clogged Exterior Dryer Vent
Exterior laundry dryer vent is clogged. Reduced airflow can affect dryer performance. Clean the vent to restore proper operation.
-
Missing GFCI Outlet
GFCI outlet is missing at this location. The circuit lacks ground‑fault protection. Install a GFCI outlet to provide required protection.
Low Findings
-
Test
-
Minor Stucco Damage
Minor damage is present on the exterior stucco. The damage could allow moisture infiltration. Monitor the area and seal any cracks as needed.
-
Trees and Signage Proximity
Trees and signage are located close to the house exterior. This proximity can limit access for exterior maintenance. Monitor clearance and trim trees or relocate signage as needed.
-
Interior Drywall Crack
Crack observed in interior drywall near stairs. The crack may allow moisture intrusion if not addressed. Seal the crack to prevent potential moisture entry.
-
Interior Windows Mid‑Life
Interior windows are from about 2006 and are mid‑to‑late in lifespan. They are not near end of life, so no immediate replacement is needed. Monitor periodically for future wear.
-
Bolted Shut Attic Hatch
Secondary attic hatch is bolted shut and inaccessible. This prevents access for inspection or maintenance. Have a qualified contractor evaluate and open the hatch.
No Concerns
-
Roof Aerial Overview
Aerial drone footage shows roof sections. No concerns were identified in this view.
-
Aerial Roof View
Aerial shot of the roof shows no concerns. No issues were identified.
-
Major Kitchen Appliances Functional
Major kitchen appliances are fully functioning and early in service life. No concerns were identified.
-
Copper Piping
Copper piping is present in the first bathroom. No concerns were identified.
-
Bathroom Condition
Bathroom shows no concerns.
-
Stand-up Shower Operational
The stand-up shower is present and appears fully functional. No concerns identified.
-
Vinyl Flooring
Vinyl flooring is present in interior areas. No concerns were identified.
-
Bedroom 1
Bedroom 1 shows no concerns. No action required.
-
Bedroom 2 Condition
Bedroom 2 shows no major concerns. No issues were identified. No action is required.
-
Bedroom 3
Bedroom 3 shows no major concerns.
-
Bedroom 4 No Concerns
Bedroom 4 shows no major concerns.
-
Bedroom 5 Electrical Panel
Bedroom 5 contains the 200‑amp electrical panel and no concerns were identified.
-
Laundry Units in Living Area
Laundry units are located in the main living room area between the living room and kitchen. Both units operate normally and no concerns were identified.
-
Secondary Laundry Units Functional
Secondary laundry units are fully functional.
-
Crawl Space Access Behind Water Heater
Access to the crawl space is located behind the main water heater and serves the venting and plumbing for the secondary suite laundry units. No concerns were identified.
-
Exterior Foundation No Cracking
Exterior foundation shows no cracking on this side of the house.
-
Daikin Heat Pump Identified
Daikin heat pump was identified; model number, year, and specifications are recorded.
-
Wood Fireplace in Living Room
Wood fireplace is present in the main living room with no major concerns.
-
200 Amp Panel with Main Breaker
A 200 amp panel with a main breaker was found in the first suite bedroom. No concerns were identified.
Standards of Practice
Inspection Exclusions
Disclaimer
Legal Statement
Table of Contents
Table of Contents
About This Report
This inspection report should be read in full. The inspection is a visual, non-invasive review of the visible and accessible portions of the property at the time of inspection. Conditions may be limited by access, weather, vegetation, stored items, furnishings, finishes, occupancy, or other site conditions.
A property does not pass or fail a home inspection. The report focuses on observed safety, function, and material conditions rather than cosmetic items or current code compliance unless specifically stated. Clients are encouraged to ask questions after reviewing the report and to complete a final walk-through before closing.
Clients should obtain as much property history as reasonably available, including seller disclosures, previous inspection or engineering reports, municipal records, insurance or lender documents, and records of repairs, renovations, additions, permits, or warranties.
Please refer to the applicable Standards of Practice for the inspector's licensing jurisdiction or professional association.
Grounds
Site and grounds observations are limited to visible and readily accessible conditions. Soil stability, slope stability, hydrological conditions, underground drainage, irrigation systems, site lighting, fencing, landscaping, retaining structures, recreational elements, and similar site features are outside the scope of a standard home inspection unless specifically included.
Drainage performance may not be fully assessable without active rainfall, and evidence of past moisture conditions may not be visible. Any comments about excluded site elements are provided as courtesy observations only.
Inspection Method
Inspection Limitations
Section Summary
Test
Roof
Roof-covering observations are based on a visual inspection of representative visible areas. The inspection provides an opinion of general condition only and does not certify that the roof is leak-proof or will remain free of future leakage.
Roof age, installation history, ventilation, exposure, drainage, debris, maintenance, and concealed underlayment all affect service life. Clients should ask the seller about roof history and consider evaluation by a qualified roofing contractor where age, condition, access, or risk warrants it.
Inspection Method
Inspection Limitations
Section Summary
Roof Corner Rot
Roof Fascia Rot
Granular Degradation Shingles
Rusty Roof Nails
Incomplete Roof Flashing
Clogged Gutters
Rufet Height Below Standard
Disconnected Upper Gutter Downspout
Roof Aerial Overview
Improperly Installed Downspout
Aerial Roof View
Improperly Installed Downspout
Exterior Areas
Inspection Method
Inspection Limitations
Section Summary
Aluminum Siding Soil Contact
Minor Stucco Damage
Trees and Signage Proximity
Stucco Crack Below Window
Exterior Window Seal Defect
Garage
Garage observations are limited to visible and readily accessible components. Stored items, vehicles, finishes, ceiling coverings, and access restrictions can conceal floors, walls, framing, electrical components, and fire-separation details.
Garage doors and openers may be checked using normal controls where safe, but force settings, concealed hardware, spring tension, and full safety performance are not determined. Door and opener concerns should be evaluated by a qualified door technician.
Inspection Method
Inspection Limitations
Section Summary
Kitchen
Kitchen and appliance observations are visual and limited. Appliances are not moved, and specialized controls, timers, thermostat calibration, self-cleaning functions, ice makers, water dispensers, portable appliances, and overall performance testing are outside the standard scope.
Dishwashers, refrigerators, microwaves, and similar appliances may be checked for visible condition, power, and basic response where accessible. Clients should verify appliance operation and satisfaction before closing.
Inspection Method
Inspection Limitations
Section Summary
Major Kitchen Appliances Functional
Kitchen Window Seals
Bathroom 1
Bathroom observations are limited to visible and readily accessible fixtures and finishes. Floor coverings, towels, bathmats, stored items, and finishes can conceal damage or moisture conditions.
Sink and tub overflows are not tested, shower pans are not flood-tested, and concealed plumbing or shower pan watertightness is outside the scope of a standard inspection. Saunas, steam baths, and other ancillary items are excluded unless specifically included.
Inspection Method
Inspection Limitations
Section Summary
Copper Piping
Bathroom 2
Bathroom observations are limited to visible and readily accessible fixtures and finishes. Floor coverings, towels, bathmats, stored items, and finishes can conceal damage or moisture conditions.
Sink and tub overflows are not tested, shower pans are not flood-tested, and concealed plumbing or shower pan watertightness is outside the scope of a standard inspection. Saunas, steam baths, and other ancillary items are excluded unless specifically included.
Inspection Method
Inspection Limitations
Section Summary
Bathroom Condition
Bathroom 3
Bathroom observations are limited to visible and readily accessible fixtures and finishes. Floor coverings, towels, bathmats, stored items, and finishes can conceal damage or moisture conditions.
Sink and tub overflows are not tested, shower pans are not flood-tested, and concealed plumbing or shower pan watertightness is outside the scope of a standard inspection. Saunas, steam baths, and other ancillary items are excluded unless specifically included.
Inspection Method
Inspection Limitations
Section Summary
Stand-up Shower Operational
Interior Areas
Interior observations are limited to visible and readily accessible walls, ceilings, floors, doors, windows, stairs, and related components. Personal belongings, furnishings, finishes, window coverings, occupancy, lighting, humidity, and temperature can limit visibility.
Obvious visible window seal failures or moisture conditions may be reported when observed, but they are not always detectable. Appliance recalls, consumer safety alerts, and concealed conditions are outside the scope of a standard inspection.
Inspection Method
Inspection Limitations
Section Summary
Interior Drywall Crack
Interior Windows Mid‑Life
Vinyl Flooring
Missing Kitchen Smoke Detector
Bedrooms
Bedroom observations are limited to visible and readily accessible walls, ceilings, floors, doors, windows, closets, electrical receptacles, and related components. Beds, furniture, stored items, window coverings, finishes, lighting, and occupancy can limit visibility.
Smoke and carbon monoxide alarms, where present, may be checked for basic response only. Concealed conditions, recalls, alarm age, and full life-safety system performance are outside the scope of a standard inspection.
Inspection Method
Inspection Limitations
Section Summary
Bedroom 1
Bedroom 2 Condition
Bedroom 3
Bedroom 4 No Concerns
Bedroom 5 Electrical Panel
Laundry
Laundry observations are visual and limited to visible and readily accessible components. Appliances are not moved, and concealed supply, drain, electrical, gas, or venting connections may not be visible.
Dryer vent condition, routing, termination, length, and lint accumulation may not be fully determined during a standard inspection. Clients should verify appliance operation and maintain dryer venting regularly.
Inspection Method
Inspection Limitations
Section Summary
Clogged Exterior Dryer Vent
Laundry Units in Living Area
Secondary Laundry Units Functional
Attic
Attic observations are limited by access, insulation, stored items, framing, height, lighting, ventilation, temperature, and safety conditions. The inspector may observe from the access opening only where entry is unsafe or impractical.
Concealed roof sheathing, air sealing, insulation continuity, venting performance, moisture history, pest activity, and asbestos-suspect materials may not be fully determined. Rodent, pest, mold, and asbestos testing are outside the standard scope.
Inspection Method
Inspection Limitations
Section Summary
Improper Duct Connection
Bolted Shut Attic Hatch
Basement/Crawlspace
Basement and crawlspace observations are limited by access, finishes, insulation, storage, moisture, lighting, height, and safety conditions. Concealed framing, floor assemblies, wall cavities, drainage components, and below-grade conditions may not be fully visible.
Moisture, drainage, structural, pest, insulation, and indoor air concerns can vary with weather and occupancy. Significant concerns should be evaluated by qualified professionals as applicable.
Inspection Method
Inspection Limitations
Section Summary
Crawl Space Access Behind Water Heater
Foundation
Foundation observations are limited to visible and readily accessible components. Finished surfaces, insulation, storage, soil, exterior grade, and other obstructions can conceal foundation conditions.
Engineering analysis, structural capacity, soil conditions, settlement evaluation, and hidden moisture conditions are outside the standard scope. Significant cracking, movement, settlement indicators, or moisture concerns should be evaluated by a qualified structural or foundation professional.
Inspection Method
Inspection Limitations
Section Summary
Exterior Foundation No Cracking
Plumbing
Water-heating observations are limited to visible and readily accessible components. The inspection does not determine internal tank condition, recovery rate, exact capacity performance, concealed venting, concealed piping, water quality, or remaining life with certainty.
Relief valves are not manually operated unless specifically noted, and hot water performance can vary with usage and settings. Water-heating concerns should be evaluated by a qualified plumbing, gas, or HVAC professional as applicable.
Inspection Method
Inspection Limitations
Section Summary
Plumbing Evaluation – Copper Supply Piping
Copper supply piping typically lasts about 50–70 years. Its lifespan depends on pipe type, water quality, pressure, temperature, installation, and corrosion conditions.
Regular maintenance can help extend the remaining serviceable life.
This may include:
- Monitor for leaks, staining, pitting, and moisture damage.
- Check visible valves, fittings, and joints.
- Maintain suitable water pressure.
- Repair leaks.
2013 Electrical Hot Water Tank
Heat/AC
Cooling and heat-pump observations are limited to visible and readily accessible equipment and normal operating controls. Systems may not be operated when outdoor temperature, site conditions, or equipment risk make operation inappropriate.
The inspection does not determine cooling capacity, refrigerant charge, internal coil condition, concealed line condition, or full performance. Service and further evaluation by a qualified HVAC contractor are recommended where condition, age, or operation is uncertain.
Inspection Method
Inspection Limitations
Section Summary
Daikin Heat Pump Identified
Wood Fireplace in Living Room
Electrical
Electrical observations are limited to visible service equipment, panels, representative outlets, switches, fixtures, and accessible components. Concealed wiring, inaccessible components, low-voltage systems, alarm systems, remote-control devices, and ancillary wiring are outside the standard scope.
Electrical concerns should be treated as potential safety or fire hazards. Repairs, corrections, or further evaluation should be performed by a qualified licensed electrician.
Inspection Method
Inspection Limitations
Section Summary
Missing GFCI Outlet
200 Amp Panel with Main Breaker
Radon Inspection
Inspection Method
Section Summary
I, John Ackerman, a licensed home inspector, prepared this report in a professional and impartial manner based on the visible and accessible conditions observed at the property on the date of inspection.